System supply
Temperature condition monitoring system
Overview
- Composed of overheat detection unit (non-contact infrared image sensor), monitoring unit, HMI program
- On-site and remote temperature monitoring of major parts of high-voltage equipment
- Collecting initial temperature rise information to prevent accidents in advance
Model | TSAS Ⅲ | TSAS Ⅳ | TSAS Ⅱ |
---|---|---|---|
Resolution | 80(D) x 60(L) = 4,800 Pixels |
120(D) x 160(L) = 19,200 Pixels |
16(D) x 4(L) = 64 Pixels |
Measurement temperature range | -10 ~ 350℃ | -20 ~ 300℃ | |
Operating temperature range | -10 ~ 60℃ | -20 ~ 70℃ | |
Accuracy | ±2% or ±2℃ of Measured value | ±2% or ±2℃ of Measured value | |
Scanning speed | 9 Hz | 0.5~8 Hz | |
Field of view | 55° x 45° | 60° x 15°{Standard) | |
Input voltage | 18~32 VDC | 8~32 VDC | |
Size | Sensor head : 20mm(D) x 50mm(L) Controller : 88mm x 69mm x 33mm Sensor head cable : Standard 3M, Max 10M | Sensor head : 14mm(D) x 32mm(L) Controller : 88mm x 69mm x 33mm Sensor head cable : Standard 3M | |
Material | Aluminum / Stainless steel | Aluminum / Stainless steel | |
Output | RS485 S-BUS 19,200~115.2K, 0-5V | RS485 Modbus, 4-20mA, 0-5V, S-BUS, K-Type Thermocouple | |
Enclosure rating | IP65(NEMA-4) | IP65(NEMA-4) |
Features
- Preventive diagnosis by monitoring power facilities in advance to check the internal temperature condition
- Monitoring the temperature of main connections (bus bars) such as switchgear and transformer
- Overheat detection system of circuit breaker contacts
Applications
- Solar power plants, wind farms, substations, factories
- Thermal power plants, combined-cycle power plants, cogeneration plants, nuclear power plants, etc.
- ESS room (container internal temperature monitoring), cable temperature monitoring
- Temperature monitoring of IPB, SWGR, GIS, bushing, transformers, battery rooms, cables, etc.